What Is the Voltage Drop for 4/0 AWG at 11A and 500 Feet?

Running 11A through 4/0 AWG copper for 500 feet on a single-phase / DC circuit produces a 0.6688-volt drop. On a 120V source that is 0.5573%; on 240V it is 0.2787%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 11A, 500ft · single-phase / DC
0.6688 V drop (0.5573% on 120V)
On 120V circuit0.5573%
On 240V circuit0.2787%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
0.67V (0.56%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 500 × 11 × 0.0608) ÷ 1000 = 0.6688 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.6688 ÷ 120) × 100 = 0.5573%
On 240V: (0.6688 ÷ 240) × 100 = 0.2787%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 11A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0334V0.0279%0.0139%OK
50ft0.0669V0.0557%0.0279%OK
75ft0.1003V0.0836%0.0418%OK
100ft0.1338V0.1115%0.0557%OK
150ft0.2006V0.1672%0.0836%OK
200ft0.2675V0.2229%0.1115%OK
300ft0.4013V0.3344%0.1672%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 11A at 500 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 11A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG0.6688V0.5573%0.2787%OK
250 kcmil0.5665V0.4721%0.236%OK
300 kcmil0.4719V0.3933%0.1966%OK
350 kcmil0.4037V0.3364%0.1682%OK
500 kcmil0.2838V0.2365%0.1183%OK
750 kcmil0.1881V0.1568%0.0784%OK

Frequently Asked Questions

4/0 AWG carrying 11A over 500ft has a 0.6688V drop (0.5573% on 120V). Reference: 0.2787% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.2787% on 240V versus 0.5573% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.5573%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.