What Is the Voltage Drop for 4/0 AWG at 124A and 200 Feet?

4/0 AWG copper carrying 124 amps over 200 feet on a single-phase / DC circuit drops 3.02 volts (2.51% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

4/0 AWG, 124A, 200ft · single-phase / DC
3.02 V drop (2.51% on 120V)
On 120V circuit2.51%
On 240V circuit1.26%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
3.02V (2.51%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 200 × 124 × 0.0608) ÷ 1000 = 3.02 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.02 ÷ 120) × 100 = 2.51%
On 240V: (3.02 ÷ 240) × 100 = 1.26%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 124A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.377V0.3141%0.1571%OK
50ft0.7539V0.6283%0.3141%OK
75ft1.13V0.9424%0.4712%OK
100ft1.51V1.26%0.6283%OK
150ft2.26V1.88%0.9424%OK
200ft3.02V2.51%1.26%OK
300ft4.52V3.77%1.88%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 124A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 124A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG3.02V2.51%1.26%OK
250 kcmil2.55V2.13%1.06%OK
300 kcmil2.13V1.77%0.8866%OK
350 kcmil1.82V1.52%0.7585%OK
500 kcmil1.28V1.07%0.5332%OK
750 kcmil0.8482V0.7068%0.3534%OK

Frequently Asked Questions

4/0 AWG carrying 124A over 200ft has a 3.02V drop (2.51% on 120V). Reference: 1.26% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.26% on 240V versus 2.51% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (2.51% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.