What Is the Voltage Drop for 4/0 AWG at 12A and 250 Feet?

Running 12A through 4/0 AWG copper for 250 feet on a single-phase / DC circuit produces a 0.3648-volt drop. On a 120V source that is 0.304%; on 240V it is 0.152%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 12A, 250ft · single-phase / DC
0.3648 V drop (0.304% on 120V)
On 120V circuit0.304%
On 240V circuit0.152%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
0.36V (0.30%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 12 × 0.0608) ÷ 1000 = 0.3648 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.3648 ÷ 120) × 100 = 0.304%
On 240V: (0.3648 ÷ 240) × 100 = 0.152%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 12A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0365V0.0304%0.0152%OK
50ft0.073V0.0608%0.0304%OK
75ft0.1094V0.0912%0.0456%OK
100ft0.1459V0.1216%0.0608%OK
150ft0.2189V0.1824%0.0912%OK
200ft0.2918V0.2432%0.1216%OK
300ft0.4378V0.3648%0.1824%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 12A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 12A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG0.3648V0.304%0.152%OK
250 kcmil0.309V0.2575%0.1288%OK
300 kcmil0.2574V0.2145%0.1072%OK
350 kcmil0.2202V0.1835%0.0918%OK
500 kcmil0.1548V0.129%0.0645%OK
750 kcmil0.1026V0.0855%0.0428%OK

Frequently Asked Questions

4/0 AWG carrying 12A over 250ft has a 0.3648V drop (0.304% on 120V). Reference: 0.152% on 240V.
On 120V, this run sits at 0.304%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.152% on 240V versus 0.304% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.304% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.