What Is the Voltage Drop for 4/0 AWG at 141A and 100 Feet?

Running 141A through 4/0 AWG copper for 100 feet on a single-phase / DC circuit produces a 1.71-volt drop. On a 120V source that is 1.43%; on 240V it is 0.7144%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 141A, 100ft · single-phase / DC
1.71 V drop (1.43% on 120V)
On 120V circuit1.43%
On 240V circuit0.7144%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
1.71V (1.43%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 141 × 0.0608) ÷ 1000 = 1.71 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.71 ÷ 120) × 100 = 1.43%
On 240V: (1.71 ÷ 240) × 100 = 0.7144%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 141A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.4286V0.3572%0.1786%OK
50ft0.8573V0.7144%0.3572%OK
75ft1.29V1.07%0.5358%OK
100ft1.71V1.43%0.7144%OK
150ft2.57V2.14%1.07%OK
200ft3.43V2.86%1.43%OK
300ft5.14V4.29%2.14%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 141A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 141A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG1.71V1.43%0.7144%OK
250 kcmil1.45V1.21%0.6051%OK
300 kcmil1.21V1.01%0.5041%OK
350 kcmil1.03V0.8625%0.4312%OK
500 kcmil0.7276V0.6063%0.3032%OK
750 kcmil0.4822V0.4019%0.2009%OK

Frequently Asked Questions

4/0 AWG carrying 141A over 100ft has a 1.71V drop (1.43% on 120V). Reference: 0.7144% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.43% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.43%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.