What Is the Voltage Drop for 4/0 AWG at 144A and 200 Feet?

4/0 AWG at 144A and 200 feet: 3.5V drop (2.92% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

4/0 AWG, 144A, 200ft · single-phase / DC
3.5 V drop (2.92% on 120V)
On 120V circuit2.92%
On 240V circuit1.46%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
3.50V (2.92%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 200 × 144 × 0.0608) ÷ 1000 = 3.5 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.5 ÷ 120) × 100 = 2.92%
On 240V: (3.5 ÷ 240) × 100 = 1.46%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 144A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.4378V0.3648%0.1824%OK
50ft0.8755V0.7296%0.3648%OK
75ft1.31V1.09%0.5472%OK
100ft1.75V1.46%0.7296%OK
150ft2.63V2.19%1.09%OK
200ft3.5V2.92%1.46%OK
300ft5.25V4.38%2.19%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 144A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 144A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG3.5V2.92%1.46%OK
250 kcmil2.97V2.47%1.24%OK
300 kcmil2.47V2.06%1.03%OK
350 kcmil2.11V1.76%0.8808%OK
500 kcmil1.49V1.24%0.6192%OK
750 kcmil0.985V0.8208%0.4104%OK

Frequently Asked Questions

4/0 AWG carrying 144A over 200ft has a 3.5V drop (2.92% on 120V). Reference: 1.46% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.46% on 240V versus 2.92% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.92%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.