What Is the Voltage Drop for 4/0 AWG at 149A and 175 Feet?

4/0 AWG copper carrying 149 amps over 175 feet on a single-phase / DC circuit drops 3.17 volts (2.64% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

4/0 AWG, 149A, 175ft · single-phase / DC
3.17 V drop (2.64% on 120V)
On 120V circuit2.64%
On 240V circuit1.32%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
3.17V (2.64%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 175 × 149 × 0.0608) ÷ 1000 = 3.17 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.17 ÷ 120) × 100 = 2.64%
On 240V: (3.17 ÷ 240) × 100 = 1.32%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 149A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.453V0.3775%0.1887%OK
50ft0.9059V0.7549%0.3775%OK
75ft1.36V1.13%0.5662%OK
100ft1.81V1.51%0.7549%OK
150ft2.72V2.26%1.13%OK
200ft3.62V3.02%1.51%Caution
300ft5.44V4.53%2.26%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 149A at 175 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 149A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG3.17V2.64%1.32%OK
250 kcmil2.69V2.24%1.12%OK
300 kcmil2.24V1.86%0.9322%OK
350 kcmil1.91V1.59%0.7975%OK
500 kcmil1.35V1.12%0.5606%OK
750 kcmil0.8918V0.7431%0.3716%OK

Frequently Asked Questions

4/0 AWG carrying 149A over 175ft has a 3.17V drop (2.64% on 120V). Reference: 1.32% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.32% on 240V versus 2.64% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (2.64% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.