What Is the Voltage Drop for 4/0 AWG at 150A and 200 Feet?
4/0 AWG at 150A and 200 feet: 3.65V drop (3.04% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge That Meets the 3% Target
The smallest gauge in our table that clears the 3% drop target at 150A over 200ft on 120V is 250 kcmil. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.
Impact of Distance
Voltage drop is proportional to distance. Here is 4/0 AWG at 150A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 0.456V | 0.38% | 0.19% | OK |
| 50ft | 0.912V | 0.76% | 0.38% | OK |
| 75ft | 1.37V | 1.14% | 0.57% | OK |
| 100ft | 1.82V | 1.52% | 0.76% | OK |
| 150ft | 2.74V | 2.28% | 1.14% | OK |
| 200ft | 3.65V | 3.04% | 1.52% | Caution |
| 300ft | 5.47V | 4.56% | 2.28% | Caution |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 150A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 150A load are listed, since thinner gauges would fail the ampacity check before drop even matters.