What Is the Voltage Drop for 4/0 AWG at 162A and 75 Feet?

4/0 AWG copper carrying 162 amps over 75 feet on a single-phase / DC circuit drops 1.48 volts (1.23% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

4/0 AWG, 162A, 75ft · single-phase / DC
1.48 V drop (1.23% on 120V)
On 120V circuit1.23%
On 240V circuit0.6156%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
1.48V (1.23%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 162 × 0.0608) ÷ 1000 = 1.48 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.48 ÷ 120) × 100 = 1.23%
On 240V: (1.48 ÷ 240) × 100 = 0.6156%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 162A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.4925V0.4104%0.2052%OK
50ft0.985V0.8208%0.4104%OK
75ft1.48V1.23%0.6156%OK
100ft1.97V1.64%0.8208%OK
150ft2.95V2.46%1.23%OK
200ft3.94V3.28%1.64%Caution
300ft5.91V4.92%2.46%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 162A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 162A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG1.48V1.23%0.6156%OK
250 kcmil1.25V1.04%0.5214%OK
300 kcmil1.04V0.8687%0.4344%OK
350 kcmil0.8918V0.7432%0.3716%OK
500 kcmil0.6269V0.5225%0.2612%OK
750 kcmil0.4155V0.3463%0.1731%OK

Frequently Asked Questions

4/0 AWG carrying 162A over 75ft has a 1.48V drop (1.23% on 120V). Reference: 0.6156% on 240V.
On 120V, this run sits at 1.23%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.6156% on 240V versus 1.23% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.23% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.