What Is the Voltage Drop for 4/0 AWG at 166A and 75 Feet?

Running 166A through 4/0 AWG copper for 75 feet on a single-phase / DC circuit produces a 1.51-volt drop. On a 120V source that is 1.26%; on 240V it is 0.6308%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 166A, 75ft · single-phase / DC
1.51 V drop (1.26% on 120V)
On 120V circuit1.26%
On 240V circuit0.6308%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
1.51V (1.26%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 166 × 0.0608) ÷ 1000 = 1.51 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.51 ÷ 120) × 100 = 1.26%
On 240V: (1.51 ÷ 240) × 100 = 0.6308%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 166A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.5046V0.4205%0.2103%OK
50ft1.01V0.8411%0.4205%OK
75ft1.51V1.26%0.6308%OK
100ft2.02V1.68%0.8411%OK
150ft3.03V2.52%1.26%OK
200ft4.04V3.36%1.68%Caution
300ft6.06V5.05%2.52%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 166A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 166A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG1.51V1.26%0.6308%OK
250 kcmil1.28V1.07%0.5343%OK
300 kcmil1.07V0.8902%0.4451%OK
350 kcmil0.9138V0.7615%0.3808%OK
500 kcmil0.6424V0.5354%0.2677%OK
750 kcmil0.4258V0.3548%0.1774%OK

Frequently Asked Questions

4/0 AWG carrying 166A over 75ft has a 1.51V drop (1.26% on 120V). Reference: 0.6308% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.26% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.26%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.