What Is the Voltage Drop for 4/0 AWG at 184A and 175 Feet?
4/0 AWG at 184A and 175 feet: 3.92V drop (3.26% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge That Meets the 3% Target
The smallest gauge in our table that clears the 3% drop target at 184A over 175ft on 120V is 250 kcmil. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.
Impact of Distance
Voltage drop is proportional to distance. Here is 4/0 AWG at 184A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 0.5594V | 0.4661% | 0.2331% | OK |
| 50ft | 1.12V | 0.9323% | 0.4661% | OK |
| 75ft | 1.68V | 1.4% | 0.6992% | OK |
| 100ft | 2.24V | 1.86% | 0.9323% | OK |
| 150ft | 3.36V | 2.8% | 1.4% | OK |
| 200ft | 4.47V | 3.73% | 1.86% | Caution |
| 300ft | 6.71V | 5.59% | 2.8% | Past 5% |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 184A at 175 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 184A load are listed, since thinner gauges would fail the ampacity check before drop even matters.