What Is the Voltage Drop for 4/0 AWG at 192A and 175 Feet?
Running 192A through 4/0 AWG copper for 175 feet on a single-phase / DC circuit produces a 4.09-volt drop. On a 120V source that is 3.4%; on 240V it is 1.7%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.
4/0 AWG, 192A, 175ft · single-phase / DC
4.09 V drop (3.4% on 120V)
On 120V circuit3.4%
On 240V circuit1.7%
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
(2 × 175 × 192 × 0.0608) ÷ 1000 = 4.09 V
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
On 120V: (4.09 ÷ 120) × 100 = 3.4%
On 240V: (4.09 ÷ 240) × 100 = 1.7%
How This Estimate Changes with Run Length and Gauge
Gauge That Meets the 3% Target
The smallest gauge in our table that clears the 3% drop target at 192A over 175ft on 120V is 250 kcmil. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.
Impact of Distance
Voltage drop is proportional to distance. Here is 4/0 AWG at 192A at different distances:
Distance
Drop (V)
% on 120V
% on 240V
NEC (120V)
25ft
0.5837V
0.4864%
0.2432%
OK
50ft
1.17V
0.9728%
0.4864%
OK
75ft
1.75V
1.46%
0.7296%
OK
100ft
2.33V
1.95%
0.9728%
OK
150ft
3.5V
2.92%
1.46%
OK
200ft
4.67V
3.89%
1.95%
Caution
300ft
7V
5.84%
2.92%
Past 5%
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 192A at 175 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 192A load are listed, since thinner gauges would fail the ampacity check before drop even matters.
4/0 AWG carrying 192A over 175ft has a 4.09V drop (3.4% on 120V). Reference: 1.7% on 240V.
Yes. Aluminum has roughly 1.3 to 1.4 times the resistance of copper at the NEC Chapter 9 Table 8 75°C reference temperature, so for the same voltage drop an aluminum conductor is typically one to two gauges larger than copper. The exact gap depends on whether ampacity or voltage drop is binding, and the install still needs anti-oxidant compound and aluminum-rated lugs.
On 120V, this run sits at 3.4%, which is past the 3% branch target; within the 5% feeder+branch total. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
This run is at 3.4% on 120V, past the 3% branch-circuit drop target. If you want to land under 3% at 192A over 175ft on 120V, the smallest gauge in our table that clears it is 250 kcmil at 2.88%. Going up one size from 4/0 AWG is not always enough, each AWG step only drops the resistance by roughly 20-25%, so on long runs or high currents you often have to skip one or two sizes to meet the target. NEC 210.19(A) Informational Note 4 frames 3% as a recommendation, not a code requirement, so the right answer for you also depends on the load (motor startup, sensitive electronics) and how much drop is tolerable.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.