What Is the Voltage Drop for 4/0 AWG at 199A and 125 Feet?

4/0 AWG copper carrying 199 amps over 125 feet on a single-phase / DC circuit drops 3.02 volts (2.52% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

4/0 AWG, 199A, 125ft · single-phase / DC
3.02 V drop (2.52% on 120V)
On 120V circuit2.52%
On 240V circuit1.26%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
3.02V (2.52%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 199 × 0.0608) ÷ 1000 = 3.02 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.02 ÷ 120) × 100 = 2.52%
On 240V: (3.02 ÷ 240) × 100 = 1.26%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 199A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.605V0.5041%0.2521%OK
50ft1.21V1.01%0.5041%OK
75ft1.81V1.51%0.7562%OK
100ft2.42V2.02%1.01%OK
150ft3.63V3.02%1.51%Caution
200ft4.84V4.03%2.02%Caution
300ft7.26V6.05%3.02%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 199A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 199A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG3.02V2.52%1.26%OK
250 kcmil2.56V2.14%1.07%OK
300 kcmil2.13V1.78%0.8893%OK
350 kcmil1.83V1.52%0.7608%OK
500 kcmil1.28V1.07%0.5348%OK
750 kcmil0.8507V0.7089%0.3545%OK

Frequently Asked Questions

4/0 AWG carrying 199A over 125ft has a 3.02V drop (2.52% on 120V). Reference: 1.26% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.26% on 240V versus 2.52% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (2.52% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.