What Is the Voltage Drop for 4/0 AWG at 19A and 250 Feet?

4/0 AWG at 19A and 250 feet: 0.5776V drop (0.4813% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

4/0 AWG, 19A, 250ft · single-phase / DC
0.5776 V drop (0.4813% on 120V)
On 120V circuit0.4813%
On 240V circuit0.2407%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
0.58V (0.48%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 19 × 0.0608) ÷ 1000 = 0.5776 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.5776 ÷ 120) × 100 = 0.4813%
On 240V: (0.5776 ÷ 240) × 100 = 0.2407%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 19A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0578V0.0481%0.0241%OK
50ft0.1155V0.0963%0.0481%OK
75ft0.1733V0.1444%0.0722%OK
100ft0.231V0.1925%0.0963%OK
150ft0.3466V0.2888%0.1444%OK
200ft0.4621V0.3851%0.1925%OK
300ft0.6931V0.5776%0.2888%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 19A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 19A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG0.5776V0.4813%0.2407%OK
250 kcmil0.4893V0.4077%0.2039%OK
300 kcmil0.4076V0.3396%0.1698%OK
350 kcmil0.3487V0.2905%0.1453%OK
500 kcmil0.2451V0.2043%0.1021%OK
750 kcmil0.1625V0.1354%0.0677%OK

Frequently Asked Questions

4/0 AWG carrying 19A over 250ft has a 0.5776V drop (0.4813% on 120V). Reference: 0.2407% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 0.4813%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.2407% on 240V versus 0.4813% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.