What Is the Voltage Drop for 4/0 AWG at 212A and 50 Feet?

Running 212A through 4/0 AWG copper for 50 feet on a single-phase / DC circuit produces a 1.29-volt drop. On a 120V source that is 1.07%; on 240V it is 0.5371%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 212A, 50ft · single-phase / DC
1.29 V drop (1.07% on 120V)
On 120V circuit1.07%
On 240V circuit0.5371%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
1.29V (1.07%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 212 × 0.0608) ÷ 1000 = 1.29 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.29 ÷ 120) × 100 = 1.07%
On 240V: (1.29 ÷ 240) × 100 = 0.5371%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 212A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.6445V0.5371%0.2685%OK
50ft1.29V1.07%0.5371%OK
75ft1.93V1.61%0.8056%OK
100ft2.58V2.15%1.07%OK
150ft3.87V3.22%1.61%Caution
200ft5.16V4.3%2.15%Caution
300ft7.73V6.44%3.22%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 212A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 212A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG1.29V1.07%0.5371%OK
250 kcmil1.09V0.9098%0.4549%OK
300 kcmil0.9095V0.7579%0.379%OK
350 kcmil0.778V0.6484%0.3242%OK
500 kcmil0.547V0.4558%0.2279%OK
750 kcmil0.3625V0.3021%0.1511%OK

Frequently Asked Questions

4/0 AWG carrying 212A over 50ft has a 1.29V drop (1.07% on 120V). Reference: 0.5371% on 240V.
On 120V, this run sits at 1.07%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.5371% on 240V versus 1.07% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.07% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.