What Is the Voltage Drop for 4/0 AWG at 24A and 300 Feet?

4/0 AWG copper carrying 24 amps over 300 feet on a single-phase / DC circuit drops 0.8755 volts (0.7296% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

4/0 AWG, 24A, 300ft · single-phase / DC
0.8755 V drop (0.7296% on 120V)
On 120V circuit0.7296%
On 240V circuit0.3648%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
0.88V (0.73%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 300 × 24 × 0.0608) ÷ 1000 = 0.8755 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.8755 ÷ 120) × 100 = 0.7296%
On 240V: (0.8755 ÷ 240) × 100 = 0.3648%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 24A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.073V0.0608%0.0304%OK
50ft0.1459V0.1216%0.0608%OK
75ft0.2189V0.1824%0.0912%OK
100ft0.2918V0.2432%0.1216%OK
150ft0.4378V0.3648%0.1824%OK
200ft0.5837V0.4864%0.2432%OK
300ft0.8755V0.7296%0.3648%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 24A at 300 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 24A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG0.8755V0.7296%0.3648%OK
250 kcmil0.7416V0.618%0.309%OK
300 kcmil0.6178V0.5148%0.2574%OK
350 kcmil0.5285V0.4404%0.2202%OK
500 kcmil0.3715V0.3096%0.1548%OK
750 kcmil0.2462V0.2052%0.1026%OK

Frequently Asked Questions

4/0 AWG carrying 24A over 300ft has a 0.8755V drop (0.7296% on 120V). Reference: 0.3648% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.3648% on 240V versus 0.7296% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.7296% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.