What Is the Voltage Drop for 4/0 AWG at 25A and 500 Feet?
4/0 AWG copper carrying 25 amps over 500 feet on a single-phase / DC circuit drops 1.52 volts (1.27% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.
Use this citation when referencing this page.
Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →
Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.
Voltage Drop Formula (single-phase / DC)
Vdrop = (2 × L × I × R) ÷ 1000
DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.
For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).
Percentage
%VD = (Vdrop ÷ Vsource) × 100
How This Estimate Changes with Run Length and Gauge
Gauge Check
4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.
Impact of Distance
Voltage drop is proportional to distance. Here is 4/0 AWG at 25A at different distances:
| Distance | Drop (V) | % on 120V | % on 240V | NEC (120V) |
|---|---|---|---|---|
| 25ft | 0.076V | 0.0633% | 0.0317% | OK |
| 50ft | 0.152V | 0.1267% | 0.0633% | OK |
| 75ft | 0.228V | 0.19% | 0.095% | OK |
| 100ft | 0.304V | 0.2533% | 0.1267% | OK |
| 150ft | 0.456V | 0.38% | 0.19% | OK |
| 200ft | 0.608V | 0.5067% | 0.2533% | OK |
| 300ft | 0.912V | 0.76% | 0.38% | OK |
Same Run, Different Wire Gauges
How does wire gauge affect voltage drop for 25A at 500 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 25A load are listed, since thinner gauges would fail the ampacity check before drop even matters.