What Is the Voltage Drop for 4/0 AWG at 26A and 100 Feet?

4/0 AWG copper carrying 26 amps over 100 feet on a single-phase / DC circuit drops 0.3162 volts (0.2635% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

4/0 AWG, 26A, 100ft · single-phase / DC
0.3162 V drop (0.2635% on 120V)
On 120V circuit0.2635%
On 240V circuit0.1317%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
0.32V (0.26%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 26 × 0.0608) ÷ 1000 = 0.3162 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.3162 ÷ 120) × 100 = 0.2635%
On 240V: (0.3162 ÷ 240) × 100 = 0.1317%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 26A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.079V0.0659%0.0329%OK
50ft0.1581V0.1317%0.0659%OK
75ft0.2371V0.1976%0.0988%OK
100ft0.3162V0.2635%0.1317%OK
150ft0.4742V0.3952%0.1976%OK
200ft0.6323V0.5269%0.2635%OK
300ft0.9485V0.7904%0.3952%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 26A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 26A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG0.3162V0.2635%0.1317%OK
250 kcmil0.2678V0.2232%0.1116%OK
300 kcmil0.2231V0.1859%0.093%OK
350 kcmil0.1908V0.159%0.0795%OK
500 kcmil0.1342V0.1118%0.0559%OK
750 kcmil0.0889V0.0741%0.0371%OK

Frequently Asked Questions

4/0 AWG carrying 26A over 100ft has a 0.3162V drop (0.2635% on 120V). Reference: 0.1317% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.2635%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.2635% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.1317% on 240V versus 0.2635% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.