What Is the Voltage Drop for 4/0 AWG at 26A and 500 Feet?

Running 26A through 4/0 AWG copper for 500 feet on a single-phase / DC circuit produces a 1.58-volt drop. On a 120V source that is 1.32%; on 240V it is 0.6587%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 26A, 500ft · single-phase / DC
1.58 V drop (1.32% on 120V)
On 120V circuit1.32%
On 240V circuit0.6587%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
1.58V (1.32%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 500 × 26 × 0.0608) ÷ 1000 = 1.58 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.58 ÷ 120) × 100 = 1.32%
On 240V: (1.58 ÷ 240) × 100 = 0.6587%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 26A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.079V0.0659%0.0329%OK
50ft0.1581V0.1317%0.0659%OK
75ft0.2371V0.1976%0.0988%OK
100ft0.3162V0.2635%0.1317%OK
150ft0.4742V0.3952%0.1976%OK
200ft0.6323V0.5269%0.2635%OK
300ft0.9485V0.7904%0.3952%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 26A at 500 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 26A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG1.58V1.32%0.6587%OK
250 kcmil1.34V1.12%0.5579%OK
300 kcmil1.12V0.9295%0.4648%OK
350 kcmil0.9542V0.7952%0.3976%OK
500 kcmil0.6708V0.559%0.2795%OK
750 kcmil0.4446V0.3705%0.1853%OK

Frequently Asked Questions

4/0 AWG carrying 26A over 500ft has a 1.58V drop (1.32% on 120V). Reference: 0.6587% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 1.32%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.6587% on 240V versus 1.32% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.