What Is the Voltage Drop for 4/0 AWG at 41A and 200 Feet?

Running 41A through 4/0 AWG copper for 200 feet on a single-phase / DC circuit produces a 0.9971-volt drop. On a 120V source that is 0.8309%; on 240V it is 0.4155%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 41A, 200ft · single-phase / DC
0.9971 V drop (0.8309% on 120V)
On 120V circuit0.8309%
On 240V circuit0.4155%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
1.00V (0.83%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 200 × 41 × 0.0608) ÷ 1000 = 0.9971 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.9971 ÷ 120) × 100 = 0.8309%
On 240V: (0.9971 ÷ 240) × 100 = 0.4155%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 41A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1246V0.1039%0.0519%OK
50ft0.2493V0.2077%0.1039%OK
75ft0.3739V0.3116%0.1558%OK
100ft0.4986V0.4155%0.2077%OK
150ft0.7478V0.6232%0.3116%OK
200ft0.9971V0.8309%0.4155%OK
300ft1.5V1.25%0.6232%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 41A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 41A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG0.9971V0.8309%0.4155%OK
250 kcmil0.8446V0.7038%0.3519%OK
300 kcmil0.7036V0.5863%0.2932%OK
350 kcmil0.6019V0.5016%0.2508%OK
500 kcmil0.4231V0.3526%0.1763%OK
750 kcmil0.2804V0.2337%0.1169%OK

Frequently Asked Questions

4/0 AWG carrying 41A over 200ft has a 0.9971V drop (0.8309% on 120V). Reference: 0.4155% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.8309% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.8309%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.