What Is the Voltage Drop for 4/0 AWG at 66A and 175 Feet?

Running 66A through 4/0 AWG copper for 175 feet on a single-phase / DC circuit produces a 1.4-volt drop. On a 120V source that is 1.17%; on 240V it is 0.5852%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 66A, 175ft · single-phase / DC
1.4 V drop (1.17% on 120V)
On 120V circuit1.17%
On 240V circuit0.5852%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
1.40V (1.17%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 175 × 66 × 0.0608) ÷ 1000 = 1.4 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.4 ÷ 120) × 100 = 1.17%
On 240V: (1.4 ÷ 240) × 100 = 0.5852%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 66A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2006V0.1672%0.0836%OK
50ft0.4013V0.3344%0.1672%OK
75ft0.6019V0.5016%0.2508%OK
100ft0.8026V0.6688%0.3344%OK
150ft1.2V1%0.5016%OK
200ft1.61V1.34%0.6688%OK
300ft2.41V2.01%1%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 66A at 175 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 66A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG1.4V1.17%0.5852%OK
250 kcmil1.19V0.9914%0.4957%OK
300 kcmil0.991V0.8258%0.4129%OK
350 kcmil0.8478V0.7065%0.3532%OK
500 kcmil0.596V0.4967%0.2483%OK
750 kcmil0.395V0.3292%0.1646%OK

Frequently Asked Questions

4/0 AWG carrying 66A over 175ft has a 1.4V drop (1.17% on 120V). Reference: 0.5852% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.17% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.17%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.