What Is the Voltage Drop for 4/0 AWG at 70A and 75 Feet?

Running 70A through 4/0 AWG copper for 75 feet on a single-phase / DC circuit produces a 0.6384-volt drop. On a 120V source that is 0.532%; on 240V it is 0.266%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 70A, 75ft · single-phase / DC
0.6384 V drop (0.532% on 120V)
On 120V circuit0.532%
On 240V circuit0.266%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
0.64V (0.53%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 70 × 0.0608) ÷ 1000 = 0.6384 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.6384 ÷ 120) × 100 = 0.532%
On 240V: (0.6384 ÷ 240) × 100 = 0.266%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 70A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2128V0.1773%0.0887%OK
50ft0.4256V0.3547%0.1773%OK
75ft0.6384V0.532%0.266%OK
100ft0.8512V0.7093%0.3547%OK
150ft1.28V1.06%0.532%OK
200ft1.7V1.42%0.7093%OK
300ft2.55V2.13%1.06%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 70A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 70A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG0.6384V0.532%0.266%OK
250 kcmil0.5408V0.4506%0.2253%OK
300 kcmil0.4504V0.3754%0.1877%OK
350 kcmil0.3854V0.3211%0.1606%OK
500 kcmil0.2709V0.2258%0.1129%OK
750 kcmil0.1796V0.1496%0.0748%OK

Frequently Asked Questions

4/0 AWG carrying 70A over 75ft has a 0.6384V drop (0.532% on 120V). Reference: 0.266% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.266% on 240V versus 0.532% on 120V.
On 120V, this run sits at 0.532%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.532% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.