What Is the Voltage Drop for 4/0 AWG at 74A and 250 Feet?

4/0 AWG copper carrying 74 amps over 250 feet on a single-phase / DC circuit drops 2.25 volts (1.87% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

4/0 AWG, 74A, 250ft · single-phase / DC
2.25 V drop (1.87% on 120V)
On 120V circuit1.87%
On 240V circuit0.9373%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
2.25V (1.87%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 74 × 0.0608) ÷ 1000 = 2.25 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.25 ÷ 120) × 100 = 1.87%
On 240V: (2.25 ÷ 240) × 100 = 0.9373%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 74A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.225V0.1875%0.0937%OK
50ft0.4499V0.3749%0.1875%OK
75ft0.6749V0.5624%0.2812%OK
100ft0.8998V0.7499%0.3749%OK
150ft1.35V1.12%0.5624%OK
200ft1.8V1.5%0.7499%OK
300ft2.7V2.25%1.12%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 74A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 74A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG2.25V1.87%0.9373%OK
250 kcmil1.91V1.59%0.794%OK
300 kcmil1.59V1.32%0.6614%OK
350 kcmil1.36V1.13%0.5658%OK
500 kcmil0.9546V0.7955%0.3978%OK
750 kcmil0.6327V0.5273%0.2636%OK

Frequently Asked Questions

4/0 AWG carrying 74A over 250ft has a 2.25V drop (1.87% on 120V). Reference: 0.9373% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.9373% on 240V versus 1.87% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.87% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.