What Is the Voltage Drop for 4/0 AWG at 76A and 50 Feet?

4/0 AWG copper carrying 76 amps over 50 feet on a single-phase / DC circuit drops 0.4621 volts (0.3851% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

4/0 AWG, 76A, 50ft · single-phase / DC
0.4621 V drop (0.3851% on 120V)
On 120V circuit0.3851%
On 240V circuit0.1925%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
0.46V (0.39%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 76 × 0.0608) ÷ 1000 = 0.4621 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.4621 ÷ 120) × 100 = 0.3851%
On 240V: (0.4621 ÷ 240) × 100 = 0.1925%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 76A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.231V0.1925%0.0963%OK
50ft0.4621V0.3851%0.1925%OK
75ft0.6931V0.5776%0.2888%OK
100ft0.9242V0.7701%0.3851%OK
150ft1.39V1.16%0.5776%OK
200ft1.85V1.54%0.7701%OK
300ft2.77V2.31%1.16%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 76A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 76A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG0.4621V0.3851%0.1925%OK
250 kcmil0.3914V0.3262%0.1631%OK
300 kcmil0.326V0.2717%0.1359%OK
350 kcmil0.2789V0.2324%0.1162%OK
500 kcmil0.1961V0.1634%0.0817%OK
750 kcmil0.13V0.1083%0.0542%OK

Frequently Asked Questions

4/0 AWG carrying 76A over 50ft has a 0.4621V drop (0.3851% on 120V). Reference: 0.1925% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.3851%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.3851% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.1925% on 240V versus 0.3851% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.