What Is the Voltage Drop for 4/0 AWG at 79A and 125 Feet?

4/0 AWG copper carrying 79 amps over 125 feet on a single-phase / DC circuit drops 1.2 volts (1% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

4/0 AWG, 79A, 125ft · single-phase / DC
1.2 V drop (1% on 120V)
On 120V circuit1%
On 240V circuit0.5003%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
1.20V (1.00%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 79 × 0.0608) ÷ 1000 = 1.2 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.2 ÷ 120) × 100 = 1%
On 240V: (1.2 ÷ 240) × 100 = 0.5003%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 79A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2402V0.2001%0.1001%OK
50ft0.4803V0.4003%0.2001%OK
75ft0.7205V0.6004%0.3002%OK
100ft0.9606V0.8005%0.4003%OK
150ft1.44V1.2%0.6004%OK
200ft1.92V1.6%0.8005%OK
300ft2.88V2.4%1.2%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 79A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 79A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG1.2V1%0.5003%OK
250 kcmil1.02V0.8476%0.4238%OK
300 kcmil0.8473V0.7061%0.353%OK
350 kcmil0.7248V0.604%0.302%OK
500 kcmil0.5096V0.4246%0.2123%OK
750 kcmil0.3377V0.2814%0.1407%OK

Frequently Asked Questions

4/0 AWG carrying 79A over 125ft has a 1.2V drop (1% on 120V). Reference: 0.5003% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.5003% on 240V versus 1% on 120V.
On 120V, this run sits at 1%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.