What Is the Voltage Drop for 4/0 AWG at 91A and 150 Feet?

Running 91A through 4/0 AWG copper for 150 feet on a single-phase / DC circuit produces a 1.66-volt drop. On a 120V source that is 1.38%; on 240V it is 0.6916%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4/0 AWG, 91A, 150ft · single-phase / DC
1.66 V drop (1.38% on 120V)
On 120V circuit1.38%
On 240V circuit0.6916%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
1.66V (1.38%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 150 × 91 × 0.0608) ÷ 1000 = 1.66 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.66 ÷ 120) × 100 = 1.38%
On 240V: (1.66 ÷ 240) × 100 = 0.6916%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 91A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2766V0.2305%0.1153%OK
50ft0.5533V0.4611%0.2305%OK
75ft0.8299V0.6916%0.3458%OK
100ft1.11V0.9221%0.4611%OK
150ft1.66V1.38%0.6916%OK
200ft2.21V1.84%0.9221%OK
300ft3.32V2.77%1.38%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 91A at 150 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 91A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG1.66V1.38%0.6916%OK
250 kcmil1.41V1.17%0.5858%OK
300 kcmil1.17V0.976%0.488%OK
350 kcmil1V0.8349%0.4175%OK
500 kcmil0.7043V0.587%0.2935%OK
750 kcmil0.4668V0.389%0.1945%OK

Frequently Asked Questions

4/0 AWG carrying 91A over 150ft has a 1.66V drop (1.38% on 120V). Reference: 0.6916% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (1.38% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.38%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.