What Is the Voltage Drop for 4/0 AWG at 96A and 50 Feet?

4/0 AWG at 96A and 50 feet: 0.5837V drop (0.4864% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

4/0 AWG, 96A, 50ft · single-phase / DC
0.5837 V drop (0.4864% on 120V)
On 120V circuit0.4864%
On 240V circuit0.2432%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4/0 AWG
0.58V (0.49%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 96 × 0.0608) ÷ 1000 = 0.5837 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.5837 ÷ 120) × 100 = 0.4864%
On 240V: (0.5837 ÷ 240) × 100 = 0.2432%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4/0 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4/0 AWG at 96A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2918V0.2432%0.1216%OK
50ft0.5837V0.4864%0.2432%OK
75ft0.8755V0.7296%0.3648%OK
100ft1.17V0.9728%0.4864%OK
150ft1.75V1.46%0.7296%OK
200ft2.33V1.95%0.9728%OK
300ft3.5V2.92%1.46%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 96A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 96A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4/0 AWG0.5837V0.4864%0.2432%OK
250 kcmil0.4944V0.412%0.206%OK
300 kcmil0.4118V0.3432%0.1716%OK
350 kcmil0.3523V0.2936%0.1468%OK
500 kcmil0.2477V0.2064%0.1032%OK
750 kcmil0.1642V0.1368%0.0684%OK

Frequently Asked Questions

4/0 AWG carrying 96A over 50ft has a 0.5837V drop (0.4864% on 120V). Reference: 0.2432% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 0.4864%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
4/0 AWG already sits within the 3% branch-circuit drop target at these inputs (0.4864% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.2432% on 240V versus 0.4864% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.