4 AWG at 100A and 200 Feet: Ampacity-Invalid Reference Calculation

Reference voltage-drop calculation only. 4 AWG is NEC-capped at 85A branch-circuit OCP per NEC 240.4(D) (75°C ampacity 85A), so 100A on this gauge fails the ampacity check before voltage drop ever enters the conversation. Do not use the number below as an install spec. As a load-side reference, 4 AWG copper at 100 amps over 200 feet on a single-phase / DC circuit would drop 12.32 volts (10.27% on 120V, 5.13% on 240V).

4 AWG, 100A, 200ft · single-phase / DC · reference only, ampacity-invalid
12.32 V drop (10.27% on 120V)
On 120V circuit10.27%
On 240V circuit5.13%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4 AWG
12.32V (10.27%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 200 × 100 × 0.308) ÷ 1000 = 12.32 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (12.32 ÷ 120) × 100 = 10.27%
On 240V: (12.32 ÷ 240) × 100 = 5.13%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

4 AWG can't carry the 100A load in the first place, its branch-circuit OCP cap is 85A under typical conditions. The smallest gauge in our table that clears both the ampacity cap and the 3% drop target at these inputs is 3/0 AWG. Run the full wire-size calculator for run length, material, and drop-target variations.

Impact of Distance

Voltage drop is proportional to distance. Here is 4 AWG at 100A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft1.54V1.28%0.6417%OK
50ft3.08V2.57%1.28%OK
75ft4.62V3.85%1.93%Caution
100ft6.16V5.13%2.57%Past 5%
150ft9.24V7.7%3.85%Past 5%
200ft12.32V10.27%5.13%Past 5%
300ft18.48V15.4%7.7%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 100A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 100A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
3 AWG9.8V8.17%4.08%Past 5%
2 AWG7.76V6.47%3.23%Past 5%
1 AWG6.16V5.13%2.57%Past 5%
1/0 AWG4.88V4.07%2.03%Caution
2/0 AWG3.87V3.22%1.61%Caution
3/0 AWG3.06V2.55%1.28%OK
4/0 AWG2.43V2.03%1.01%OK
250 kcmil2.06V1.72%0.8583%OK
300 kcmil1.72V1.43%0.715%OK
350 kcmil1.47V1.22%0.6117%OK
500 kcmil1.03V0.86%0.43%OK
750 kcmil0.684V0.57%0.285%OK

Frequently Asked Questions

4 AWG carrying 100A over 200ft has a 12.32V drop (10.27% on 120V), but 4 AWG is NEC-capped at 85A branch-circuit OCP per NEC 240.4(D), so 100A on 4 AWG is ampacity-invalid and the drop figure above is a reference calculation only, not an install spec. Reference: 5.13% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 5.13% on 240V versus 10.27% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 10.27%, which is past both the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements. However, 4 AWG is ampacity-invalid for 100A (NEC 240.4(D) caps 4 AWG at 85A branch-circuit OCP), so this is a reference drop calculation only and the 3% check does not make this a valid install.
This run is at 10.27% on 120V, past the 3% branch-circuit drop target. If you want to land under 3% at 100A over 200ft on 120V, the smallest gauge in our table that clears it is 3/0 AWG at 2.55%. Going up one size from 4 AWG is not always enough, each AWG step only drops the resistance by roughly 20-25%, so on long runs or high currents you often have to skip one or two sizes to meet the target. NEC 210.19(A) Informational Note 4 frames 3% as a recommendation, not a code requirement, so the right answer for you also depends on the load (motor startup, sensitive electronics) and how much drop is tolerable.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.