What Is the Voltage Drop for 4 AWG at 11A and 125 Feet?

Running 11A through 4 AWG copper for 125 feet on a single-phase / DC circuit produces a 0.847-volt drop. On a 120V source that is 0.7058%; on 240V it is 0.3529%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4 AWG, 11A, 125ft · single-phase / DC
0.847 V drop (0.7058% on 120V)
On 120V circuit0.7058%
On 240V circuit0.3529%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4 AWG
0.85V (0.71%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 11 × 0.308) ÷ 1000 = 0.847 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.847 ÷ 120) × 100 = 0.7058%
On 240V: (0.847 ÷ 240) × 100 = 0.3529%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4 AWG at 11A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1694V0.1412%0.0706%OK
50ft0.3388V0.2823%0.1412%OK
75ft0.5082V0.4235%0.2118%OK
100ft0.6776V0.5647%0.2823%OK
150ft1.02V0.847%0.4235%OK
200ft1.36V1.13%0.5647%OK
300ft2.03V1.69%0.847%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 11A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 11A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4 AWG0.847V0.7058%0.3529%OK
3 AWG0.6738V0.5615%0.2807%OK
2 AWG0.5335V0.4446%0.2223%OK
1 AWG0.4235V0.3529%0.1765%OK
1/0 AWG0.3355V0.2796%0.1398%OK
2/0 AWG0.2659V0.2216%0.1108%OK

Frequently Asked Questions

4 AWG carrying 11A over 125ft has a 0.847V drop (0.7058% on 120V). Reference: 0.3529% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.7058%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.3529% on 240V versus 0.7058% on 120V.
4 AWG already sits within the 3% branch-circuit drop target at these inputs (0.7058% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.