What Is the Voltage Drop for 4 AWG at 12A and 250 Feet?

Running 12A through 4 AWG copper for 250 feet on a single-phase / DC circuit produces a 1.85-volt drop. On a 120V source that is 1.54%; on 240V it is 0.77%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4 AWG, 12A, 250ft · single-phase / DC
1.85 V drop (1.54% on 120V)
On 120V circuit1.54%
On 240V circuit0.77%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4 AWG
1.85V (1.54%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 250 × 12 × 0.308) ÷ 1000 = 1.85 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.85 ÷ 120) × 100 = 1.54%
On 240V: (1.85 ÷ 240) × 100 = 0.77%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4 AWG at 12A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.1848V0.154%0.077%OK
50ft0.3696V0.308%0.154%OK
75ft0.5544V0.462%0.231%OK
100ft0.7392V0.616%0.308%OK
150ft1.11V0.924%0.462%OK
200ft1.48V1.23%0.616%OK
300ft2.22V1.85%0.924%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 12A at 250 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 12A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4 AWG1.85V1.54%0.77%OK
3 AWG1.47V1.23%0.6125%OK
2 AWG1.16V0.97%0.485%OK
1 AWG0.924V0.77%0.385%OK
1/0 AWG0.732V0.61%0.305%OK
2/0 AWG0.5802V0.4835%0.2418%OK

Frequently Asked Questions

4 AWG carrying 12A over 250ft has a 1.85V drop (1.54% on 120V). Reference: 0.77% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 1.54%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.77% on 240V versus 1.54% on 120V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.