What Is the Voltage Drop for 4 AWG at 22A and 175 Feet?

4 AWG at 22A and 175 feet: 2.37V drop (1.98% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

4 AWG, 22A, 175ft · single-phase / DC
2.37 V drop (1.98% on 120V)
On 120V circuit1.98%
On 240V circuit0.9882%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4 AWG
2.37V (1.98%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 175 × 22 × 0.308) ÷ 1000 = 2.37 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.37 ÷ 120) × 100 = 1.98%
On 240V: (2.37 ÷ 240) × 100 = 0.9882%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4 AWG at 22A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.3388V0.2823%0.1412%OK
50ft0.6776V0.5647%0.2823%OK
75ft1.02V0.847%0.4235%OK
100ft1.36V1.13%0.5647%OK
150ft2.03V1.69%0.847%OK
200ft2.71V2.26%1.13%OK
300ft4.07V3.39%1.69%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 22A at 175 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 22A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4 AWG2.37V1.98%0.9882%OK
3 AWG1.89V1.57%0.786%OK
2 AWG1.49V1.24%0.6224%OK
1 AWG1.19V0.9882%0.4941%OK
1/0 AWG0.9394V0.7828%0.3914%OK
2/0 AWG0.7446V0.6205%0.3102%OK

Frequently Asked Questions

4 AWG carrying 22A over 175ft has a 2.37V drop (1.98% on 120V). Reference: 0.9882% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.9882% on 240V versus 1.98% on 120V.
On 120V, this run sits at 1.98%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
4 AWG already sits within the 3% branch-circuit drop target at these inputs (1.98% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.