What Is the Voltage Drop for 4 AWG at 5A and 100 Feet?

4 AWG copper carrying 5 amps over 100 feet on a single-phase / DC circuit drops 0.308 volts (0.2567% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

4 AWG, 5A, 100ft · single-phase / DC
0.308 V drop (0.2567% on 120V)
On 120V circuit0.2567%
On 240V circuit0.1283%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4 AWG
0.31V (0.26%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 5 × 0.308) ÷ 1000 = 0.308 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.308 ÷ 120) × 100 = 0.2567%
On 240V: (0.308 ÷ 240) × 100 = 0.1283%

How This Estimate Changes with Run Length and Gauge

Gauge Check

4 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 4 AWG at 5A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.077V0.0642%0.0321%OK
50ft0.154V0.1283%0.0642%OK
75ft0.231V0.1925%0.0963%OK
100ft0.308V0.2567%0.1283%OK
150ft0.462V0.385%0.1925%OK
200ft0.616V0.5133%0.2567%OK
300ft0.924V0.77%0.385%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 5A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 5A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4 AWG0.308V0.2567%0.1283%OK
3 AWG0.245V0.2042%0.1021%OK
2 AWG0.194V0.1617%0.0808%OK
1 AWG0.154V0.1283%0.0642%OK
1/0 AWG0.122V0.1017%0.0508%OK
2/0 AWG0.0967V0.0806%0.0403%OK

Frequently Asked Questions

4 AWG carrying 5A over 100ft has a 0.308V drop (0.2567% on 120V). Reference: 0.1283% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
4 AWG already sits within the 3% branch-circuit drop target at these inputs (0.2567% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
On 120V, this run sits at 0.2567%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.1283% on 240V versus 0.2567% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.