What Is the Voltage Drop for 4 AWG at 80A and 200 Feet?

Running 80A through 4 AWG copper for 200 feet on a single-phase / DC circuit produces a 9.86-volt drop. On a 120V source that is 8.21%; on 240V it is 4.11%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

4 AWG, 80A, 200ft · single-phase / DC
9.86 V drop (8.21% on 120V)
On 120V circuit8.21%
On 240V circuit4.11%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

4 AWG
9.86V (8.21%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 200 × 80 × 0.308) ÷ 1000 = 9.86 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (9.86 ÷ 120) × 100 = 8.21%
On 240V: (9.86 ÷ 240) × 100 = 4.11%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

The smallest gauge in our table that clears the 3% drop target at 80A over 200ft on 120V is 2/0 AWG. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.

Impact of Distance

Voltage drop is proportional to distance. Here is 4 AWG at 80A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft1.23V1.03%0.5133%OK
50ft2.46V2.05%1.03%OK
75ft3.7V3.08%1.54%Caution
100ft4.93V4.11%2.05%Caution
150ft7.39V6.16%3.08%Past 5%
200ft9.86V8.21%4.11%Past 5%
300ft14.78V12.32%6.16%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 80A at 200 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 80A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
4 AWG9.86V8.21%4.11%Past 5%
3 AWG7.84V6.53%3.27%Past 5%
2 AWG6.21V5.17%2.59%Past 5%
1 AWG4.93V4.11%2.05%Caution
1/0 AWG3.9V3.25%1.63%Caution
2/0 AWG3.09V2.58%1.29%OK

Frequently Asked Questions

4 AWG carrying 80A over 200ft has a 9.86V drop (8.21% on 120V). Reference: 4.11% on 240V.
On 120V, this run sits at 8.21%, which is past both the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 4.11% on 240V versus 8.21% on 120V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.