What Is the Voltage Drop for 6 AWG at 12A and 125 Feet?

6 AWG at 12A and 125 feet: 1.47V drop (1.23% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

6 AWG, 12A, 125ft · single-phase / DC
1.47 V drop (1.23% on 120V)
On 120V circuit1.23%
On 240V circuit0.6138%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

6 AWG
1.47V (1.23%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 12 × 0.491) ÷ 1000 = 1.47 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.47 ÷ 120) × 100 = 1.23%
On 240V: (1.47 ÷ 240) × 100 = 0.6138%

How This Estimate Changes with Run Length and Gauge

Gauge Check

6 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 6 AWG at 12A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.2946V0.2455%0.1228%OK
50ft0.5892V0.491%0.2455%OK
75ft0.8838V0.7365%0.3682%OK
100ft1.18V0.982%0.491%OK
150ft1.77V1.47%0.7365%OK
200ft2.36V1.96%0.982%OK
300ft3.54V2.95%1.47%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 12A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 12A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
6 AWG1.47V1.23%0.6138%OK
4 AWG0.924V0.77%0.385%OK
3 AWG0.735V0.6125%0.3063%OK
2 AWG0.582V0.485%0.2425%OK
1 AWG0.462V0.385%0.1925%OK
1/0 AWG0.366V0.305%0.1525%OK

Frequently Asked Questions

6 AWG carrying 12A over 125ft has a 1.47V drop (1.23% on 120V). Reference: 0.6138% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 1.23%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
6 AWG already sits within the 3% branch-circuit drop target at these inputs (1.23% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.6138% on 240V versus 1.23% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.