What Is the Voltage Drop for 6 AWG at 28A and 125 Feet?

6 AWG copper carrying 28 amps over 125 feet on a single-phase / DC circuit drops 3.44 volts (2.86% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

6 AWG, 28A, 125ft · single-phase / DC
3.44 V drop (2.86% on 120V)
On 120V circuit2.86%
On 240V circuit1.43%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

6 AWG
3.44V (2.86%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 28 × 0.491) ÷ 1000 = 3.44 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.44 ÷ 120) × 100 = 2.86%
On 240V: (3.44 ÷ 240) × 100 = 1.43%

How This Estimate Changes with Run Length and Gauge

Gauge Check

6 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 6 AWG at 28A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.6874V0.5728%0.2864%OK
50ft1.37V1.15%0.5728%OK
75ft2.06V1.72%0.8593%OK
100ft2.75V2.29%1.15%OK
150ft4.12V3.44%1.72%Caution
200ft5.5V4.58%2.29%Caution
300ft8.25V6.87%3.44%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 28A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 28A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
6 AWG3.44V2.86%1.43%OK
4 AWG2.16V1.8%0.8983%OK
3 AWG1.72V1.43%0.7146%OK
2 AWG1.36V1.13%0.5658%OK
1 AWG1.08V0.8983%0.4492%OK
1/0 AWG0.854V0.7117%0.3558%OK

Frequently Asked Questions

6 AWG carrying 28A over 125ft has a 3.44V drop (2.86% on 120V). Reference: 1.43% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 2.86%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.43% on 240V versus 2.86% on 120V.
6 AWG already sits within the 3% branch-circuit drop target at these inputs (2.86% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.