What Is the Voltage Drop for 6 AWG at 36A and 100 Feet?

Running 36A through 6 AWG copper for 100 feet on a single-phase / DC circuit produces a 3.54-volt drop. On a 120V source that is 2.95%; on 240V it is 1.47%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

6 AWG, 36A, 100ft · single-phase / DC
3.54 V drop (2.95% on 120V)
On 120V circuit2.95%
On 240V circuit1.47%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

6 AWG
3.54V (2.95%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 36 × 0.491) ÷ 1000 = 3.54 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.54 ÷ 120) × 100 = 2.95%
On 240V: (3.54 ÷ 240) × 100 = 1.47%

How This Estimate Changes with Run Length and Gauge

Gauge Check

6 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 6 AWG at 36A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.8838V0.7365%0.3682%OK
50ft1.77V1.47%0.7365%OK
75ft2.65V2.21%1.1%OK
100ft3.54V2.95%1.47%OK
150ft5.3V4.42%2.21%Caution
200ft7.07V5.89%2.95%Past 5%
300ft10.61V8.84%4.42%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 36A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 36A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
6 AWG3.54V2.95%1.47%OK
4 AWG2.22V1.85%0.924%OK
3 AWG1.76V1.47%0.735%OK
2 AWG1.4V1.16%0.582%OK
1 AWG1.11V0.924%0.462%OK
1/0 AWG0.8784V0.732%0.366%OK

Frequently Asked Questions

6 AWG carrying 36A over 100ft has a 3.54V drop (2.95% on 120V). Reference: 1.47% on 240V.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.47% on 240V versus 2.95% on 120V.
On 120V, this run sits at 2.95%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
6 AWG already sits within the 3% branch-circuit drop target at these inputs (2.95% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.