What Is the Voltage Drop for 6 AWG at 54A and 25 Feet?

Running 54A through 6 AWG copper for 25 feet on a single-phase / DC circuit produces a 1.33-volt drop. On a 120V source that is 1.1%; on 240V it is 0.5524%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

6 AWG, 54A, 25ft · single-phase / DC
1.33 V drop (1.1% on 120V)
On 120V circuit1.1%
On 240V circuit0.5524%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

6 AWG
1.33V (1.10%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 54 × 0.491) ÷ 1000 = 1.33 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.33 ÷ 120) × 100 = 1.1%
On 240V: (1.33 ÷ 240) × 100 = 0.5524%

How This Estimate Changes with Run Length and Gauge

Gauge Check

6 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 6 AWG at 54A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft1.33V1.1%0.5524%OK
50ft2.65V2.21%1.1%OK
75ft3.98V3.31%1.66%Caution
100ft5.3V4.42%2.21%Caution
150ft7.95V6.63%3.31%Past 5%
200ft10.61V8.84%4.42%Past 5%
300ft15.91V13.26%6.63%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 54A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 54A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
6 AWG1.33V1.1%0.5524%OK
4 AWG0.8316V0.693%0.3465%OK
3 AWG0.6615V0.5513%0.2756%OK
2 AWG0.5238V0.4365%0.2183%OK
1 AWG0.4158V0.3465%0.1733%OK
1/0 AWG0.3294V0.2745%0.1372%OK

Frequently Asked Questions

6 AWG carrying 54A over 25ft has a 1.33V drop (1.1% on 120V). Reference: 0.5524% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
6 AWG already sits within the 3% branch-circuit drop target at these inputs (1.1% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.1%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.