What Is the Voltage Drop for 6 AWG at 54A and 75 Feet?

6 AWG copper carrying 54 amps over 75 feet on a single-phase / DC circuit drops 3.98 volts (3.31% on a 120V source). This sits past the 3% target NEC 210.19(A) Informational Note 4 cites for branch circuits, but within the 5% target for feeder+branch total. Which one applies depends on whether this run is a branch circuit, a feeder, or a feeder+branch combined: if it's a branch circuit, it's past target; if it's a feeder alone or part of a feeder+branch combined system, the 5% total is the figure to check against whatever the upstream drop adds. Both are planning targets, not code requirements.

6 AWG, 54A, 75ft · single-phase / DC
3.98 V drop (3.31% on 120V)
On 120V circuit3.31%
On 240V circuit1.66%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

6 AWG
3.98V (3.31%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 54 × 0.491) ÷ 1000 = 3.98 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (3.98 ÷ 120) × 100 = 3.31%
On 240V: (3.98 ÷ 240) × 100 = 1.66%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

The smallest gauge in our table that clears the 3% drop target at 54A over 75ft on 120V is 4 AWG. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.

Impact of Distance

Voltage drop is proportional to distance. Here is 6 AWG at 54A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft1.33V1.1%0.5524%OK
50ft2.65V2.21%1.1%OK
75ft3.98V3.31%1.66%Caution
100ft5.3V4.42%2.21%Caution
150ft7.95V6.63%3.31%Past 5%
200ft10.61V8.84%4.42%Past 5%
300ft15.91V13.26%6.63%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 54A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 54A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
6 AWG3.98V3.31%1.66%Caution
4 AWG2.49V2.08%1.04%OK
3 AWG1.98V1.65%0.8269%OK
2 AWG1.57V1.31%0.6548%OK
1 AWG1.25V1.04%0.5197%OK
1/0 AWG0.9882V0.8235%0.4117%OK

Frequently Asked Questions

6 AWG carrying 54A over 75ft has a 3.98V drop (3.31% on 120V). Reference: 1.66% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
This run is at 3.31% on 120V, past the 3% branch-circuit drop target. If you want to land under 3% at 54A over 75ft on 120V, the smallest gauge in our table that clears it is 4 AWG at 2.08%. Going up one size from 6 AWG is not always enough, each AWG step only drops the resistance by roughly 20-25%, so on long runs or high currents you often have to skip one or two sizes to meet the target. NEC 210.19(A) Informational Note 4 frames 3% as a recommendation, not a code requirement, so the right answer for you also depends on the load (motor startup, sensitive electronics) and how much drop is tolerable.
On 120V, this run sits at 3.31%, which is past the 3% branch target; within the 5% feeder+branch total. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.66% on 240V versus 3.31% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.