What Is the Voltage Drop for 8 AWG at 10A and 125 Feet?

8 AWG copper carrying 10 amps over 125 feet on a single-phase / DC circuit drops 1.95 volts (1.62% on a 120V source). This sits within the 3% branch target and the 5% feeder+branch total target that NEC 210.19(A) Informational Note 4 cites. Both are planning targets, not code requirements.

8 AWG, 10A, 125ft · single-phase / DC
1.95 V drop (1.62% on 120V)
On 120V circuit1.62%
On 240V circuit0.8104%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

8 AWG
1.95V (1.62%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 125 × 10 × 0.778) ÷ 1000 = 1.95 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (1.95 ÷ 120) × 100 = 1.62%
On 240V: (1.95 ÷ 240) × 100 = 0.8104%

How This Estimate Changes with Run Length and Gauge

Gauge Check

8 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 8 AWG at 10A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.389V0.3242%0.1621%OK
50ft0.778V0.6483%0.3242%OK
75ft1.17V0.9725%0.4863%OK
100ft1.56V1.3%0.6483%OK
150ft2.33V1.95%0.9725%OK
200ft3.11V2.59%1.3%OK
300ft4.67V3.89%1.95%Caution

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 10A at 125 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 10A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
8 AWG1.95V1.62%0.8104%OK
6 AWG1.23V1.02%0.5115%OK
4 AWG0.77V0.6417%0.3208%OK
3 AWG0.6125V0.5104%0.2552%OK
2 AWG0.485V0.4042%0.2021%OK
1 AWG0.385V0.3208%0.1604%OK

Frequently Asked Questions

8 AWG carrying 10A over 125ft has a 1.95V drop (1.62% on 120V). Reference: 0.8104% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
On 120V, this run sits at 1.62%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
8 AWG already sits within the 3% branch-circuit drop target at these inputs (1.62% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.8104% on 240V versus 1.62% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.