What Is the Voltage Drop for 8 AWG at 13A and 25 Feet?

8 AWG at 13A and 25 feet: 0.5057V drop (0.4214% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

8 AWG, 13A, 25ft · single-phase / DC
0.5057 V drop (0.4214% on 120V)
On 120V circuit0.4214%
On 240V circuit0.2107%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

8 AWG
0.51V (0.42%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 25 × 13 × 0.778) ÷ 1000 = 0.5057 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.5057 ÷ 120) × 100 = 0.4214%
On 240V: (0.5057 ÷ 240) × 100 = 0.2107%

How This Estimate Changes with Run Length and Gauge

Gauge Check

8 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 8 AWG at 13A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.5057V0.4214%0.2107%OK
50ft1.01V0.8428%0.4214%OK
75ft1.52V1.26%0.6321%OK
100ft2.02V1.69%0.8428%OK
150ft3.03V2.53%1.26%OK
200ft4.05V3.37%1.69%Caution
300ft6.07V5.06%2.53%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 13A at 25 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 13A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
8 AWG0.5057V0.4214%0.2107%OK
6 AWG0.3192V0.266%0.133%OK
4 AWG0.2002V0.1668%0.0834%OK
3 AWG0.1593V0.1327%0.0664%OK
2 AWG0.1261V0.1051%0.0525%OK
1 AWG0.1001V0.0834%0.0417%OK

Frequently Asked Questions

8 AWG carrying 13A over 25ft has a 0.5057V drop (0.4214% on 120V). Reference: 0.2107% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
8 AWG already sits within the 3% branch-circuit drop target at these inputs (0.4214% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.2107% on 240V versus 0.4214% on 120V.
On 120V, this run sits at 0.4214%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.