What Is the Voltage Drop for 8 AWG at 15A and 100 Feet?

Running 15A through 8 AWG copper for 100 feet on a single-phase / DC circuit produces a 2.33-volt drop. On a 120V source that is 1.95%; on 240V it is 0.9725%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

8 AWG, 15A, 100ft · single-phase / DC
2.33 V drop (1.95% on 120V)
On 120V circuit1.95%
On 240V circuit0.9725%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

8 AWG
2.33V (1.95%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 15 × 0.778) ÷ 1000 = 2.33 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.33 ÷ 120) × 100 = 1.95%
On 240V: (2.33 ÷ 240) × 100 = 0.9725%

How This Estimate Changes with Run Length and Gauge

Gauge Check

8 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 8 AWG at 15A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.5835V0.4863%0.2431%OK
50ft1.17V0.9725%0.4863%OK
75ft1.75V1.46%0.7294%OK
100ft2.33V1.95%0.9725%OK
150ft3.5V2.92%1.46%OK
200ft4.67V3.89%1.95%Caution
300ft7V5.84%2.92%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 15A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 15A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
8 AWG2.33V1.95%0.9725%OK
6 AWG1.47V1.23%0.6138%OK
4 AWG0.924V0.77%0.385%OK
3 AWG0.735V0.6125%0.3063%OK
2 AWG0.582V0.485%0.2425%OK
1 AWG0.462V0.385%0.1925%OK

Frequently Asked Questions

8 AWG carrying 15A over 100ft has a 2.33V drop (1.95% on 120V). Reference: 0.9725% on 240V.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.95%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
8 AWG already sits within the 3% branch-circuit drop target at these inputs (1.95% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 0.9725% on 240V versus 1.95% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.