What Is the Voltage Drop for 8 AWG at 27A and 100 Feet?

Running 27A through 8 AWG copper for 100 feet on a single-phase / DC circuit produces a 4.2-volt drop. On a 120V source that is 3.5%; on 240V it is 1.75%. NEC 210.19(A) Informational Note 4 recommends keeping branch-circuit drop at or below 3% and total feeder+branch drop at or below 5%, these are performance recommendations, not code requirements.

8 AWG, 27A, 100ft · single-phase / DC
4.2 V drop (3.5% on 120V)
On 120V circuit3.5%
On 240V circuit1.75%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

8 AWG
4.20V (3.50%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 100 × 27 × 0.778) ÷ 1000 = 4.2 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (4.2 ÷ 120) × 100 = 3.5%
On 240V: (4.2 ÷ 240) × 100 = 1.75%

How This Estimate Changes with Run Length and Gauge

Gauge That Meets the 3% Target

The smallest gauge in our table that clears the 3% drop target at 27A over 100ft on 120V is 6 AWG. Shorter runs, higher source voltage, or a higher drop tolerance (feeder-only applications often accept up to 5%) can change the pick. Run the full wire-size calculator with your actual variables.

Impact of Distance

Voltage drop is proportional to distance. Here is 8 AWG at 27A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft1.05V0.8753%0.4376%OK
50ft2.1V1.75%0.8753%OK
75ft3.15V2.63%1.31%OK
100ft4.2V3.5%1.75%Caution
150ft6.3V5.25%2.63%Past 5%
200ft8.4V7%3.5%Past 5%
300ft12.6V10.5%5.25%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 27A at 100 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 27A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
8 AWG4.2V3.5%1.75%Caution
6 AWG2.65V2.21%1.1%OK
4 AWG1.66V1.39%0.693%OK
3 AWG1.32V1.1%0.5513%OK
2 AWG1.05V0.873%0.4365%OK
1 AWG0.8316V0.693%0.3465%OK

Frequently Asked Questions

8 AWG carrying 27A over 100ft has a 4.2V drop (3.5% on 120V). Reference: 1.75% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
This run is at 3.5% on 120V, past the 3% branch-circuit drop target. If you want to land under 3% at 27A over 100ft on 120V, the smallest gauge in our table that clears it is 6 AWG at 2.21%. Going up one size from 8 AWG is not always enough, each AWG step only drops the resistance by roughly 20-25%, so on long runs or high currents you often have to skip one or two sizes to meet the target. NEC 210.19(A) Informational Note 4 frames 3% as a recommendation, not a code requirement, so the right answer for you also depends on the load (motor startup, sensitive electronics) and how much drop is tolerable.
On 120V, this run sits at 3.5%, which is past the 3% branch target; within the 5% feeder+branch total. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
Same wire, same amps, same distance: the volts dropped are identical. But the percentage is worse on 120V because the drop is a larger fraction of the source voltage. This run would be 1.75% on 240V versus 3.5% on 120V.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.