What Is the Voltage Drop for 8 AWG at 27A and 50 Feet?

8 AWG at 27A and 50 feet: 2.1V drop (1.75% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

8 AWG, 27A, 50ft · single-phase / DC
2.1 V drop (1.75% on 120V)
On 120V circuit1.75%
On 240V circuit0.8753%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

8 AWG
2.10V (1.75%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 50 × 27 × 0.778) ÷ 1000 = 2.1 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (2.1 ÷ 120) × 100 = 1.75%
On 240V: (2.1 ÷ 240) × 100 = 0.8753%

How This Estimate Changes with Run Length and Gauge

Gauge Check

8 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 8 AWG at 27A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft1.05V0.8753%0.4376%OK
50ft2.1V1.75%0.8753%OK
75ft3.15V2.63%1.31%OK
100ft4.2V3.5%1.75%Caution
150ft6.3V5.25%2.63%Past 5%
200ft8.4V7%3.5%Past 5%
300ft12.6V10.5%5.25%Past 5%

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 27A at 50 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 27A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
8 AWG2.1V1.75%0.8753%OK
6 AWG1.33V1.1%0.5524%OK
4 AWG0.8316V0.693%0.3465%OK
3 AWG0.6615V0.5513%0.2756%OK
2 AWG0.5238V0.4365%0.2183%OK
1 AWG0.4158V0.3465%0.1733%OK

Frequently Asked Questions

8 AWG carrying 27A over 50ft has a 2.1V drop (1.75% on 120V). Reference: 0.8753% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
8 AWG already sits within the 3% branch-circuit drop target at these inputs (1.75% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 1.75%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.