What Is the Voltage Drop for 8 AWG at 2A and 75 Feet?

8 AWG at 2A and 75 feet: 0.2334V drop (0.1945% on 120V), computed on the single-phase / DC basis. Every conductor has resistance, and longer runs at higher currents drop more voltage. Use this calculation to check whether your run clears the 3% branch-circuit drop target before pulling wire.

8 AWG, 2A, 75ft · single-phase / DC
0.2334 V drop (0.1945% on 120V)
On 120V circuit0.1945%
On 240V circuit0.0972%

Circuit basis: This uses the single-phase / DC round-trip formula (factor of 2) for the voltage drop across the two circuit conductors. For a three-phase line-to-line run use the three-phase version of the page (append ?type=3ph). Switch to the three-phase version →

8 AWG
0.23V (0.19%)

Assumes a 120V source on a single-phase / DC circuit. Use the circuit-basis link above to switch between single-phase/DC and three-phase.

Voltage Drop Formula (single-phase / DC)

Vdrop = (2 × L × I × R) ÷ 1000

(2 × 75 × 2 × 0.778) ÷ 1000 = 0.2334 V

DC and single-phase AC use the round-trip factor of 2. Current travels out to the load on one conductor and returns on another.

For a three-phase circuit at the same amps and distance, see the three-phase version (uses √3 instead of 2, so the drop is about 13.4% lower).

Percentage

%VD = (Vdrop ÷ Vsource) × 100

On 120V: (0.2334 ÷ 120) × 100 = 0.1945%
On 240V: (0.2334 ÷ 240) × 100 = 0.0972%

How This Estimate Changes with Run Length and Gauge

Gauge Check

8 AWG clears the 3% drop target at these inputs. A smaller conductor may also meet it with less margin. See the minimum gauge for this load and distance.

Impact of Distance

Voltage drop is proportional to distance. Here is 8 AWG at 2A at different distances:

DistanceDrop (V)% on 120V% on 240VNEC (120V)
25ft0.0778V0.0648%0.0324%OK
50ft0.1556V0.1297%0.0648%OK
75ft0.2334V0.1945%0.0972%OK
100ft0.3112V0.2593%0.1297%OK
150ft0.4668V0.389%0.1945%OK
200ft0.6224V0.5187%0.2593%OK
300ft0.9336V0.778%0.389%OK

Same Run, Different Wire Gauges

How does wire gauge affect voltage drop for 2A at 75 feet on 120V single-phase / DC? Only gauges whose branch-circuit OCP cap is at or above the 2A load are listed, since thinner gauges would fail the ampacity check before drop even matters.

GaugeDrop (V)% on 120V% on 240V3% Target (120V)
8 AWG0.2334V0.1945%0.0972%OK
6 AWG0.1473V0.1228%0.0614%OK
4 AWG0.0924V0.077%0.0385%OK
3 AWG0.0735V0.0613%0.0306%OK
2 AWG0.0582V0.0485%0.0243%OK
1 AWG0.0462V0.0385%0.0193%OK

Frequently Asked Questions

8 AWG carrying 2A over 75ft has a 0.2334V drop (0.1945% on 120V). Reference: 0.0972% on 240V.
Motors run hotter and can have trouble starting under load. Incandescent and halogen lighting dims. Some electronics misbehave at the low end of their input tolerance. Energy is wasted as I²R heating in the conductor. These are performance issues; high drop is not itself a code violation unless the specific installation cites a hard limit.
8 AWG already sits within the 3% branch-circuit drop target at these inputs (0.1945% on 120V). Going to a larger gauge is only useful if you want more headroom for future load growth, longer runs, or tighter drop targets like the 5% feeder+branch total recommendation used in sensitive or motor-heavy installations.
Voltage drop is proportional to distance. The formula multiplies by 2 × the distance (out and back). Doubling the run doubles the drop.
On 120V, this run sits at 0.1945%, which is within the 3% branch and 5% feeder+branch total drop targets. NEC 210.19(A) Informational Note 4 cites 3% for branch circuits and 5% for total feeder+branch drop as performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.