What Wire Size for 1.42 Amps at 175 Feet?
14 AWG copper is a typical pick for 1.42A at 175 feet on 120V under a 3% drop target. It balances NEC branch-circuit ampacity and voltage drop over distance. Drop with 14 AWG at these inputs: 1.56V (1.3%). Real-world sizing also depends on insulation temperature rating, cable type, and install conditions.
No aluminum row: every aluminum size in our reference table sits past the 3% drop target at 175 feet on 120V, or the amperage is below the 30A residential threshold where aluminum is not a typical pick. On a higher source voltage, a shorter run, or a looser drop target, aluminum is still the standard feeder material at higher amperages.
Use this citation when referencing this page.
Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →
How Wire Size Is Determined
Step 1: NEC Branch-Circuit Ampacity
The conductor needs to carry at least 1.42A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 14 AWG sits at a branch-circuit OCP of 15A because the NEC 240.4(D) small-conductor rule caps it below the 20A 75°C ampacity table value. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (14 AWG NM-B = 15A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.
Step 2: Voltage Drop Check
%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)
NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.
Practical Information
What If You Go One Size Smaller?
The recommended gauge is already the smallest suitable option in our table.
What If You Go One Size Larger?
Using 12 AWG (one size thicker) would reduce voltage drop to 0.9841V (0.8201% on 120V). More expensive wire but better performance and more headroom for future load increases.
Wattage at This Amperage
1.42A at 120V delivers 170.4 watts (DC / resistive load). See conversion.