What Wire Size for 102.3 Amps at 25 Feet?

For a 102.3-amp circuit running 25 feet on 120V, 2 AWG copper is the smallest gauge in our table that both stays within the 3% drop target and covers the branch-circuit OCP cap for 102.3A. A shorter run of 25 feet at the same voltage often allows 2 AWG. Treat this as an estimate, not an install spec.

102.3A at 25ft · 120V three-phase L-L · 3% drop target
2 AWG copper
Aluminum option1/0 AWG
On a 240V circuit (copper)2 AWG
Voltage drop (120V, copper)0.8593V (0.7161%)
check_circle Within the 3% branch and 5% feeder+branch total drop targets
2 AWG Cu / 1/0 AWG Al

Assumes a 120V source on a three-phase L-L circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to single-phase / DC →

How Wire Size Is Determined

Step 1: NEC Branch-Circuit Ampacity

2 AWG branch-circuit OCP (115A) ≥ 102.3A ✓

The conductor needs to carry at least 102.3A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 2 AWG sits at a branch-circuit OCP of 115A. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (2 AWG NM-B = 95A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.

Step 2: Voltage Drop Check

%VD = (√3 × L × I × R) ÷ (1000 × V) × 100 (three-phase L-L; √3 factor)

(√3 × 25 × 102.3 × 0.194) ÷ (1000 × 120) × 100 = 0.7161%

NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.

Practical Information

What If You Go One Size Smaller?

Using 3 AWG (one size thinner) at these inputs gives a voltage drop of 1.09V (0.9044% on 120V), and its branch-circuit OCP cap under typical conditions is 100A.

Limiting factor here: branch-circuit ampacity. 3 AWG has a branch-circuit OCP cap of 100A under the typical 75°C-termination assumptions used here, which is below the 102.3A load. For this load it shouldn't be used without reassessing against the actual termination temperature, cable type, ambient conditions, and any 240.4(D) or 240.4(B) provisions.

What If You Go One Size Larger?

Using 1 AWG (one size thicker) would reduce voltage drop to 0.6822V (0.5685% on 120V). More expensive wire but better performance and more headroom for future load increases.

Wattage at This Amperage

102.3A at 120V delivers 12,276 watts (DC / resistive load). See conversion.

Frequently Asked Questions

102.3A at 25ft on 120V is commonly served by 2 AWG copper to land under the 3% voltage-drop target, under the typical 75°C-termination assumptions used in this table. Actual install sizing also depends on conductor material, insulation and termination temperature rating, cable type, ambient and bundling conditions, and local code.
NEC 210.19(A) (branch circuits) and 215.3 (feeders) size the conductor and overcurrent device at not less than 125% of the continuous load plus 100% of any non-continuous load. For a 102.3A continuous load that points the sizing math at the 127.88A figure, but the actual conductor and breaker pick still depends on termination temperature rating, cable type, bundling and ambient conditions, and any 240.4(D) or 240.4(B) provisions. Treat this as the input to a sizing decision, not the output.
Copper wire pricing tracks the LME copper spot price and varies with insulation type, cable assembly (THHN, NM-B, MC, SE, USE), and quantity. Check current pricing with a local electrical supply house or distributor catalog; commodity-driven numbers inlined on a calculator page age quickly.
Yes, but you may need thicker wire. At 50ft on 120V, check the wire size calculator. You may need to go up one or two gauges.
NEC 210.19(A) Informational Note 4 recommends ≤3% for branch circuits and ≤5% total (feeder + branch). These are performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.