What Wire Size for 127.88 Amps at 75 Feet?
For a 127.88-amp circuit running 75 feet on 120V, 1 AWG copper is the smallest gauge in our table that both stays within the 3% drop target and covers the branch-circuit OCP cap for 127.88A. A shorter run of 37.5 feet at the same voltage often allows 1 AWG. Treat this as an estimate, not an install spec.
Use this citation when referencing this page.
Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →
How Wire Size Is Determined
Step 1: NEC Branch-Circuit Ampacity
The conductor needs to carry at least 127.88A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 1 AWG sits at a branch-circuit OCP of 130A. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (1 AWG NM-B = 110A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.
Step 2: Voltage Drop Check
%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)
NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.
Practical Information
What If You Go One Size Smaller?
Using 2 AWG (one size thinner) at these inputs gives a voltage drop of 3.72V (3.1% on 120V), and its branch-circuit OCP cap under typical conditions is 115A.
Limiting factor here: branch-circuit ampacity. 2 AWG has a branch-circuit OCP cap of 115A under the typical 75°C-termination assumptions used here, which is below the 127.88A load. For this load it shouldn't be used without reassessing against the actual termination temperature, cable type, ambient conditions, and any 240.4(D) or 240.4(B) provisions.
What If You Go One Size Larger?
Using 1/0 AWG (one size thicker) would reduce voltage drop to 2.34V (1.95% on 120V). More expensive wire but better performance and more headroom for future load increases.
Wattage at This Amperage
127.88A at 120V delivers 15,345.6 watts (DC / resistive load). See conversion.