What Wire Size for 13.25 Amps at 25 Feet?

14 AWG copper is a typical pick for 13.25A at 25 feet on 120V under a 3% drop target. It balances NEC branch-circuit ampacity and voltage drop over distance. Drop with 14 AWG at these inputs: 2.08V (1.73%). Real-world sizing also depends on insulation temperature rating, cable type, and install conditions.

13.25A at 25ft · 120V single-phase / DC · 3% drop target
14 AWG copper
On a 240V circuit (copper)14 AWG
Voltage drop (120V, copper)2.08V (1.73%)

No aluminum row: every aluminum size in our reference table sits past the 3% drop target at 25 feet on 120V, or the amperage is below the 30A residential threshold where aluminum is not a typical pick. On a higher source voltage, a shorter run, or a looser drop target, aluminum is still the standard feeder material at higher amperages.

check_circle Within the 3% branch and 5% feeder+branch total drop targets
14 AWG Cu

Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →

How Wire Size Is Determined

Step 1: NEC Branch-Circuit Ampacity

14 AWG branch-circuit OCP (15A under NEC 240.4(D)) ≥ 13.25A ✓

The conductor needs to carry at least 13.25A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 14 AWG sits at a branch-circuit OCP of 15A because the NEC 240.4(D) small-conductor rule caps it below the 20A 75°C ampacity table value. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (14 AWG NM-B = 15A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.

Step 2: Voltage Drop Check

%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)

(2 × 25 × 13.25 × 3.14) ÷ (1000 × 120) × 100 = 1.73%

NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.

Practical Information

What If You Go One Size Smaller?

The recommended gauge is already the smallest suitable option in our table.

What If You Go One Size Larger?

Using 12 AWG (one size thicker) would reduce voltage drop to 1.31V (1.09% on 120V). More expensive wire but better performance and more headroom for future load increases.

Wattage at This Amperage

13.25A at 120V delivers 1,590 watts (DC / resistive load). See conversion.

Frequently Asked Questions

13.25A at 25ft on 120V is commonly served by 14 AWG copper to land under the 3% voltage-drop target, under the typical 75°C-termination assumptions used in this table. Actual install sizing also depends on conductor material, insulation and termination temperature rating, cable type, ambient and bundling conditions, and local code.
Copper wire pricing tracks the LME copper spot price and varies with insulation type, cable assembly (THHN, NM-B, MC, SE, USE), and quantity. Check current pricing with a local electrical supply house or distributor catalog; commodity-driven numbers inlined on a calculator page age quickly.
NEC 210.19(A) Informational Note 4 recommends ≤3% for branch circuits and ≤5% total (feeder + branch). These are performance recommendations, not hard code requirements.
Yes, but you may need thicker wire. At 50ft on 120V, check the wire size calculator. You may need to go up one or two gauges.
NEC 210.19(A) (branch circuits) and 215.3 (feeders) size the conductor and overcurrent device at not less than 125% of the continuous load plus 100% of any non-continuous load. For a 13.25A continuous load that points the sizing math at the 16.56A figure, but the actual conductor and breaker pick still depends on termination temperature rating, cable type, bundling and ambient conditions, and any 240.4(D) or 240.4(B) provisions. Treat this as the input to a sizing decision, not the output.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.