What Wire Size for 14.15 Amps at 250 Feet?

For 14.15 amps at 250 feet on a 120V circuit, 6 AWG copper is a common starting point under a 3% voltage-drop target. On a 240V circuit the same current often allows 8 AWG, because the 3% allowable drop is a larger number of volts at higher source voltage. Actual install sizing still depends on conductor material, insulation/termination temperature, cable type, ambient and bundling conditions, and local code.

14.15A at 250ft · 120V single-phase / DC · 3% drop target
6 AWG copper
On a 240V circuit (copper)8 AWG
Voltage drop (120V, copper)3.47V (2.89%)

No aluminum row: every aluminum size in our reference table sits past the 3% drop target at 250 feet on 120V, or the amperage is below the 30A residential threshold where aluminum is not a typical pick. On a higher source voltage, a shorter run, or a looser drop target, aluminum is still the standard feeder material at higher amperages.

check_circle Within the 3% branch and 5% feeder+branch total drop targets
6 AWG Cu

Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →

How Wire Size Is Determined

Step 1: NEC Branch-Circuit Ampacity

6 AWG branch-circuit OCP (65A) ≥ 14.15A ✓

The conductor needs to carry at least 14.15A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 6 AWG sits at a branch-circuit OCP of 65A. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (6 AWG NM-B = 55A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.

Step 2: Voltage Drop Check

%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)

(2 × 250 × 14.15 × 0.491) ÷ (1000 × 120) × 100 = 2.89%

NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.

Practical Information

What If You Go One Size Smaller?

Using 8 AWG (one size thinner) at these inputs gives a voltage drop of 5.5V (4.59% on 120V), and its branch-circuit OCP cap under typical conditions is 50A.

Limiting factor here: voltage drop, not ampacity. 8 AWG is still above the 14.15A load at its 50A branch-circuit OCP cap, so the conductor temperature margin is fine for this run. What pushes it off this page's pick is the 4.59% drop sitting past the 3% target, which is a performance recommendation (NEC 210.19(A) Informational Note 4), not a code requirement. On shorter runs or at higher source voltage the same gauge would often clear the drop target too.

What If You Go One Size Larger?

Using 4 AWG (one size thicker) would reduce voltage drop to 2.18V (1.82% on 120V). More expensive wire but better performance and more headroom for future load increases.

Wattage at This Amperage

14.15A at 120V delivers 1,698 watts (DC / resistive load). See conversion.

Frequently Asked Questions

14.15A at 250ft on 120V is commonly served by 6 AWG copper to land under the 3% voltage-drop target, under the typical 75°C-termination assumptions used in this table. Actual install sizing also depends on conductor material, insulation and termination temperature rating, cable type, ambient and bundling conditions, and local code.
NEC 210.19(A) (branch circuits) and 215.3 (feeders) size the conductor and overcurrent device at not less than 125% of the continuous load plus 100% of any non-continuous load. For a 14.15A continuous load that points the sizing math at the 17.69A figure, but the actual conductor and breaker pick still depends on termination temperature rating, cable type, bundling and ambient conditions, and any 240.4(D) or 240.4(B) provisions. Treat this as the input to a sizing decision, not the output.
Voltage drop scales linearly with distance: doubling the one-way run length doubles the drop in volts. At 14.15A on 120V, a 250ft run is often served by 6 AWG to land under the 3% drop target, a run half that length can sometimes use one gauge thinner, and a run double that length usually needs one or two gauges thicker. Ampacity is set by the conductor itself (Table 310.16 at the applicable termination temperature), so the binding constraint is ampacity on short runs and voltage drop on long runs.
Yes, but you may need thicker wire. At 500ft on 120V, check the wire size calculator. You may need to go up one or two gauges.
NEC 210.19(A) Informational Note 4 recommends ≤3% for branch circuits and ≤5% total (feeder + branch). These are performance recommendations, not hard code requirements.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.