What Wire Size for 15.91 Amps at 400 Feet?

For a 15.91-amp circuit running 400 feet on 120V, 3 AWG copper is the smallest gauge in our table that both stays within the 3% drop target and covers the branch-circuit OCP cap for 15.91A. A shorter run of 200 feet at the same voltage often allows 6 AWG. Treat this as an estimate, not an install spec.

15.91A at 400ft · 120V single-phase / DC · 3% drop target
3 AWG copper
On a 240V circuit (copper)6 AWG
Voltage drop (120V, copper)3.12V (2.6%)

No aluminum row: every aluminum size in our reference table sits past the 3% drop target at 400 feet on 120V, or the amperage is below the 30A residential threshold where aluminum is not a typical pick. On a higher source voltage, a shorter run, or a looser drop target, aluminum is still the standard feeder material at higher amperages.

check_circle Within the 3% branch and 5% feeder+branch total drop targets
3 AWG Cu

Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →

How Wire Size Is Determined

Step 1: NEC Branch-Circuit Ampacity

3 AWG branch-circuit OCP (100A) ≥ 15.91A ✓

The conductor needs to carry at least 15.91A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 3 AWG sits at a branch-circuit OCP of 100A. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (3 AWG NM-B = 85A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.

Step 2: Voltage Drop Check

%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)

(2 × 400 × 15.91 × 0.245) ÷ (1000 × 120) × 100 = 2.6%

NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.

Practical Information

What If You Go One Size Smaller?

Using 4 AWG (one size thinner) at these inputs gives a voltage drop of 3.92V (3.27% on 120V), and its branch-circuit OCP cap under typical conditions is 85A.

Limiting factor here: voltage drop, not ampacity. 4 AWG is still above the 15.91A load at its 85A branch-circuit OCP cap, so the conductor temperature margin is fine for this run. What pushes it off this page's pick is the 3.27% drop sitting past the 3% target, which is a performance recommendation (NEC 210.19(A) Informational Note 4), not a code requirement. On shorter runs or at higher source voltage the same gauge would often clear the drop target too.

What If You Go One Size Larger?

Using 2 AWG (one size thicker) would reduce voltage drop to 2.47V (2.06% on 120V). More expensive wire but better performance and more headroom for future load increases.

Wattage at This Amperage

15.91A at 120V delivers 1,909.2 watts (DC / resistive load). See conversion.

Frequently Asked Questions

15.91A at 400ft on 120V is commonly served by 3 AWG copper to land under the 3% voltage-drop target, under the typical 75°C-termination assumptions used in this table. Actual install sizing also depends on conductor material, insulation and termination temperature rating, cable type, ambient and bundling conditions, and local code.
Copper and aluminum are picked independently against the same drop target on this site; neither pick implies ampacity equivalence with the other. At 15.91A residential branch-circuit territory, copper is the default. Aluminum in 14/12/10 AWG is not typical for residential branches, both for code reasons (the NEC 240.4(D) small-conductor rule caps aluminum branch OCP tighter than copper) and because termination and anti-oxidation requirements add cost at that scale.
NEC 210.19(A) Informational Note 4 recommends ≤3% for branch circuits and ≤5% total (feeder + branch). These are performance recommendations, not hard code requirements.
Copper wire pricing tracks the LME copper spot price and varies with insulation type, cable assembly (THHN, NM-B, MC, SE, USE), and quantity. Check current pricing with a local electrical supply house or distributor catalog; commodity-driven numbers inlined on a calculator page age quickly.
NEC 210.19(A) (branch circuits) and 215.3 (feeders) size the conductor and overcurrent device at not less than 125% of the continuous load plus 100% of any non-continuous load. For a 15.91A continuous load that points the sizing math at the 19.89A figure, but the actual conductor and breaker pick still depends on termination temperature rating, cable type, bundling and ambient conditions, and any 240.4(D) or 240.4(B) provisions. Treat this as the input to a sizing decision, not the output.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.