What Wire Size for 171.57 Amps at 175 Feet?

For a 171.57-amp circuit running 175 feet on 120V, 250 kcmil copper is the smallest gauge in our table that both stays within the 3% drop target and covers the branch-circuit OCP cap for 171.57A. A shorter run of 87.5 feet at the same voltage often allows 2/0 AWG. Treat this as an estimate, not an install spec.

171.57A at 175ft · 120V single-phase / DC · 3% drop target
250 kcmil copper
Aluminum option500 kcmil
On a 240V circuit (copper)2/0 AWG
Voltage drop (120V, copper)3.09V (2.58%)
check_circle Within the 3% branch and 5% feeder+branch total drop targets
250 kcmil Cu / 500 kcmil Al

Assumes a 120V source on a single-phase / DC circuit and a 3% voltage-drop target. Each material is picked independently against the same target, so the copper and aluminum results are two separate recommendations, not an ampacity equivalence. Switch to three-phase L-L →

How Wire Size Is Determined

Step 1: NEC Branch-Circuit Ampacity

250 kcmil branch-circuit OCP (255A) ≥ 171.57A ✓

The conductor needs to carry at least 171.57A without going past its temperature rating, and the OCP protecting it needs to respect the NEC branch-circuit cap. Under the typical assumptions used in this table (copper, 75°C termination, no bundling or ambient derates), 250 kcmil sits at a branch-circuit OCP of 255A. That is not a universal number: NM-B cable (Romex) follows the 60°C column in residential use per NEC 334.80 (250 kcmil NM-B = 215A), bundling more than three current-carrying conductors requires a 310.15(C)(1) adjustment, ambient temperatures above 30°C require a 310.15(B) correction, and 60°C terminations on typical residential equipment can pull the usable value lower still. Use the nameplate and local code for the actual install value.

Step 2: Voltage Drop Check

%VD = (2 × L × I × R) ÷ (1000 × V) × 100 (single-phase / DC; round-trip factor of 2)

(2 × 175 × 171.57 × 0.0515) ÷ (1000 × 120) × 100 = 2.58%

NEC 210.19(A) Informational Note 4 recommends ≤ 3% for branch circuits and ≤ 5% for feeder + branch total as performance targets, not hard code requirements. This run sits within the 3% target used for this calculation.

Practical Information

What If You Go One Size Smaller?

Using 4/0 AWG (one size thinner) at these inputs gives a voltage drop of 3.65V (3.04% on 120V), and its branch-circuit OCP cap under typical conditions is 230A.

Limiting factor here: voltage drop, not ampacity. 4/0 AWG is still above the 171.57A load at its 230A branch-circuit OCP cap, so the conductor temperature margin is fine for this run. What pushes it off this page's pick is the 3.04% drop sitting past the 3% target, which is a performance recommendation (NEC 210.19(A) Informational Note 4), not a code requirement. On shorter runs or at higher source voltage the same gauge would often clear the drop target too.

What If You Go One Size Larger?

Using 300 kcmil (one size thicker) would reduce voltage drop to 2.58V (2.15% on 120V). More expensive wire but better performance and more headroom for future load increases.

Wattage at This Amperage

171.57A at 120V delivers 20,588.4 watts (DC / resistive load). See conversion.

Frequently Asked Questions

171.57A at 175ft on 120V is commonly served by 250 kcmil copper to land under the 3% voltage-drop target, under the typical 75°C-termination assumptions used in this table. Actual install sizing also depends on conductor material, insulation and termination temperature rating, cable type, ambient and bundling conditions, and local code.
NEC 210.19(A) (branch circuits) and 215.3 (feeders) size the conductor and overcurrent device at not less than 125% of the continuous load plus 100% of any non-continuous load. For a 171.57A continuous load that points the sizing math at the 214.46A figure, but the actual conductor and breaker pick still depends on termination temperature rating, cable type, bundling and ambient conditions, and any 240.4(D) or 240.4(B) provisions. Treat this as the input to a sizing decision, not the output.
It depends on which factor the thinner gauge violates. If its branch-circuit ampacity is still at or above the load, the limiting factor is usually voltage drop (a performance recommendation per NEC 210.19(A) Informational Note 4, not a hard code requirement) and the symptom is dimming lights, motor startup issues, or wasted energy as I²R losses. If the thinner gauge is actually below the load's ampacity ceiling at the relevant termination temperature, that is a conductor-heating / code compliance issue, and the wire should not be used for that load. A calculator page cannot tell you which category applies to your install: verify against the conductor type, termination temperature, and install conditions.
Yes, but you may need thicker wire. At 350ft on 120V, check the wire size calculator. You may need to go up one or two gauges.
Voltage drop scales linearly with distance: doubling the one-way run length doubles the drop in volts. At 171.57A on 120V, a 175ft run is often served by 250 kcmil to land under the 3% drop target, a run half that length can sometimes use one gauge thinner, and a run double that length usually needs one or two gauges thicker. Ampacity is set by the conductor itself (Table 310.16 at the applicable termination temperature), so the binding constraint is ampacity on short runs and voltage drop on long runs.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.